EN1101

PDU Level
- PDU Metered: Yes
- Energy (kWh) Meter: Yes
- PDU level Billing Grade Metering: Yes
Outlet Level
- Outlet Metered: No
- Outlet level Billing Grade Metering: No
- Outlet Level Switching: No
External Sensor Compatibility
- Maximum number of sensors: 6
- Temperature sensor compatible: Yes
- Temp + Humidity sensor compatible: Yes
- 3T + 1H sensor compatible: Yes
- Dry contact sensor compatible: Yes
- Fluid leak sensor compatible: Yes
Network Intelligence Module
- Field Replaceable Network Intelligence Module: Yes
- Hot Swappable: Yes
Design Features
- Color coded outlets: Yes
- Locking IEC Outlets: Yes
- Rewireable Input Cord: No
- Toolless Mounting Systems: Yes
- Daisy Chain Capable: Yes
- Circuit Breaker Status Monitoring: No
Single-phase 16A input with (24)C13 outlets
Power Input
- Acceptable Input Voltage: 220-240 VAC +6%, -10%
- Input Current per Phase: 16A
- Phase Type: 1-phase
- Maximum Input Power(kVA): 3.84
- Input Frequency(Hz): 50
- Input Plug: IEC309 316P6
- Input Cord Length: 3.0m
Output Power Configuration
- Output Voltage: 220-240 VAC
- Total Number of Outlets: 24
- Total # of IEC C13 Outlets: 24
- Total # of BS1363 Outlets:
- Total # of CEE7/4 Schuko Outlets:
- Total # of CEE7/5 Outlets:
- Total # of AS3112/CCC Outlets:
- Total # of NEMA 5-20R Outlets:
- Total # of Japan Locking 15A Outlets:
- Type of Circuit Breaker: n/a
- Maximum Current per Outlet: 10A
Physical Characteristics
- Length : 1065 mm
- Depth : 44 mm
- Width : 55 mm
- Chassis Color: Black
Environmental Characteristics
- Temperature Range, Operating: -5 to 60°C
- Humidity Range, Operating: 5-95% RH, non-condensing
- Maximum Elevation, Operating: 0-3,000 m
- Storage Temperature Range: -25 to 65°C
- Storage Humidity Range: 5-95% RH, non-condensing
- Storage Maximum Elevation: 0-15,000 m
Compliance Approvals
- UL: No
- EMC: Yes
- Safety: TÜV approved, EN/IEC 60950-1
- Environmental: ROHS, Contains No SVHCs, WEEE
- Product Sheet